UKOOA TYPE FM / TYPE FP 150/250V Fire Resistant

Application

These cables are designed for fixed installation for control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.

Standards

  • BS 6883/BS 7917/UKOOA
  • IEC 60331-21
  • IEC 60332-3-22 CAT. A
  • IEC 60332-1
  • IEC 60754-1 & IEC 60754-2
  • IEC 61034-1 & IEC 61034-2

Construction

Conductors Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228.
Fire Protection Mica glass tape
Insulation EPR complying with BS7655 GP4
Drain Wire Tinned copper drain wire
Individual Screen Aluminium mylar tape screen
Bedding CSP – SW2 compound complying with BS 7655
Armour Galvanised steel wire braid to BS 6883
Outer Sheath CSP – SW2 compound complying with BS 7655 (TYPE FM: Blue; TYPE FP: Grey).

Dimensions and Weight

Construction
No. of cores×Cross section(mm^2)
Nominal Insulation Thickness
mm
Nominal Thickness of Inner Sheath
mm
Nominal Thickness of Outer Sheath
mm
Mominal Overall Diameter
mm
Approx. Weight
kg/km
3×2×0.75 0.8 1.2 1.4 18.6 580
7×2×0.75 0.8 1.4 1.6 23.2 915
12×2×0.75 0.8 1.6 1.8 29.7 1420
20×2×0.75 0.8 2.1 2.7 40.1 2905
3×3×0.75 0.8 1.3 1.5 20.4 700
7×3×0.75 0.8 1.5 1.7 26.6 1180
12×3×0.75 0.8 1.9 2.2 38.5 2550
1×4×0.75 0.8 1.2 1.3 14.6 360
1×2×1.0 0.8 1.0 1.2 13.0 295
1×3×1.0 0.8 1.0 1.2 13.6 330
1×4×1.0 0.8 1.0 1.3 15.9 380
3×2×1.5 0.8 1.3 1.4 21.6 732
7×2×1.5 0.8 1.4 1.6 27.8 1242
12×2×1.5 0.8 1.7 1.9 36.4 2039
3×3×1.5 0.8 1.3 1.5 24.5 780
7×3×1.5 0.8 1.5 1.7 32.1 1409
12×3×1.5 0.8 1.8 2.0 43.9 2301